Choose the dwelling rules
For a ramped approach to an Irish dwelling, use TGD M 2022, §3.1.2.4. Its limits differ from the Table 2 rules for other buildings. Do not use Table 2 as the dwelling table.
| Dwelling approach gradient | Maximum run between level landings |
|---|---|
| 1:20 to 1:15, including 1:15 | 10 m |
| Steeper than 1:15, up to 1:12 | 5 m |
Use the shallowest slope the site allows. Landings need at least 1200 mm clear length, outside any door or gate swing. Provide them between flights and at changes of direction. Section 3.1.2.1 sets at least 900 mm clear route width and 2100 mm headroom.
Other requirements still apply, including guarding and rails under TGD K. A stepped route has its own conditions in §3.1.2.5 where a level, gentle or ramped approach is not practicable. Do not treat that as a free choice.
Worked example
For a 450 mm rise at 1:15, horizontal run is:
450 × 15 = 6750 mm, or 6.75 m.
That is within the dwelling route’s 10 m flight limit. Add the landings and check the whole layout. This sum does not approve the design.
Sources
Source checked on 6 September 2026. Confirm the edition and transition rules for the job. This is not a professional access audit.
Related building rules
More Ireland rules
Ramps in other countries
- House Ramp Gradients: Choose the Right NCC Path
- US Ramp Slopes (IRC R311.8)
- NZ Ramp Gradients (NZBC D1)
- UK Ramp Gradients (Approved Document M)
- Canada Ramp Slopes (NBC 9.8)
- French Ramp Rules: Housing Access and Terrace Exceptions
- German Ramp Gradients: DIN 18040-2 Accessible Ramp Rules
- Spanish Ramp Gradients: General Ramp vs Accessible Itinerary (CTE DB-SUA)
- Indonesian Ramp Gradients: Indoor, Outdoor & Landings
- Japanese Ramp Gradients: Slope, Landings & Width
- Indian Ramp Guidance: NBC 2016 Scope and Gradients
- Norwegian Ramp Gradients: TEK17 §12-16
- Swedish Ramp Gradients: Accessible Routes and the 1:12 Limit