The requirement
A stair has to be steep enough to fit the space, but shallow enough to climb safely. For a private stair in a home, Approved Document K sets this with two numbers you set out on site — the rise and the going — plus a limit on how steep the whole flight can be.
- Rise — how tall each step is.
- Going — how deep each step is, measured from the front edge of one step to the front edge of the next.
Each step must rise no more than 220 mm and no less than 150 mm. The going must be at least 220 mm, up to 300 mm. An external stair to a home needs a going of 280 mm or more. Whatever rise and going you pick, the flight must not be steeper than a pitch of 42°. Every step in the flight should be the same rise and the same going — one odd step is where people trip.
| Dimension | Limit (Approved Document K, England) |
|---|---|
| Rise | max 220 mm · min 150 mm |
| Going | max 300 mm · min 220 mm (external ≥ 280 mm) |
| Pitch | max 42° |
| Headroom | min 2000 mm (2 m) |
| Handrail height | 900–1000 mm above the pitch line |
| Width | not set by Doc K for a private stair — see below |
Headroom over the whole stair must be at least 2000 mm (2 m). There is one concession for a loft conversion where you cannot get the full height: 1.9 m at the side of the stair, dropping to 1.8 m at the centre.
You need a handrail where there is a drop. Fit it 900–1000 mm above the pitch line (the line that runs across the front edges of the steps). If the flight is 1000 mm wide or more, put a handrail on both sides.
On width, Approved Document K does not set a minimum for an ordinary private stair. Practical guidance (BS 5395) points to around 800–900 mm, but treat that as guidance, not a Doc K requirement — the code leaves it open.
Guards & barriers
Guarding is the barrier that stops a fall from the edge of a stair, landing or floor. Approved Document K sets when you need it and how high it goes.
| Where | Guarding height (Approved Document K, England) |
|---|---|
| Stairs, landings and ramps | 900 mm |
| Internal floor edges | 900 mm |
| External balconies and roof edges | 1100 mm |
You need guarding wherever the drop is more than 600 mm. For the gaps in the guarding: a 100 mm sphere must not be able to pass through. And where children under 5 may use the stair — which includes homes — the guarding must not be easy to climb, so avoid horizontal rails or footholds a child could use as a ladder.
Work it out on site
Say your floor-to-floor height is 2640 mm and you want an even set of steps.
- Pick how many risers. 2640 ÷ 220 (the tallest a rise can be) = 12. So you need at least 12 risers. 2640 ÷ 12 = 220 mm per step — right on the limit. Add one to be comfortable: 2640 ÷ 13 = 203 mm per step. Better.
- Pick a going. Try 250 mm — inside the 220–300 range.
- Check the pitch. A 203 mm rise over a 250 mm going is well under the 42° limit, so the flight is fine.
Change the number of risers or the going until the rise sits comfortably under 220 mm and the pitch stays under 42°. The calculator does this in one go.
Do it in 5 seconds
Related
- UK building regulations: rules by nation — how the code works across England, Wales, Scotland and Northern Ireland.
- NCC stairs for chippies (Australia) — the same job under Australian rules, if you build in both places.
Sources
- Approved Document K, Protection from falling, collision and impact (2013 edition, England), Table 1.1 — rise, going, pitch, headroom, handrail and guarding for a private stair. Read it at gov.uk. (Confirmed against Approved Document K, verified 2026-07-28.)
- Adoption / edition caveat: these are England’s figures from Approved Document K (2013). Building rules in the UK are devolved. Wales runs a parallel Approved Document K that currently matches, but can change. Scotland uses the Building Standards Technical Handbook and Northern Ireland uses Technical Booklet H — separate documents with their own numbers, not shown here. Doc K is guidance showing one way to meet the Building Regulations; check the current edition and confirm which nation the job is in before you rely on any figure.
State variations
These states apply requirements that differ from the national provisions for this rule.
- Scotland Adopted Approved Document K
Current code: Technical Handbook - Domestic (April 2026)
Scotland's Technical Handbook requires a deeper going (225 mm) and allows lower handrails and in-dwelling stair guarding (840 mm) than England's Doc K.